Tagged With "Eddy Probe Compatibility"

Reply

Re: Magnet Mounted accelerometer near Eddy current probes.

John from PA ·
[Added subject matter] Two proximity probes mounted at 90° on a relatively small shaft can exhibit cross talk. Since the probe tip spacing varies based on probe type, it is best to check the probe OEM manual for recommendations.
Reply

Re: Magnet Mounted accelerometer near Eddy current probes.

William_C._Foiles ·
A steady field may have little effect, but the act of placing the magnetic near a prox probe would not be static.
Topic

Magnet Mounted accelerometer near Eddy current probes.

Rohit02 ·
Dear Experts, A question just clicked my mind that can there be a disturbance in eddy current probe output, if a magnet mount sensor is placed near it during portable data collection(Casing Vibrations)? Regards
Reply

Re: Magnet Mounted accelerometer near Eddy current probes.

John from PA ·
There would be minimal effect on a proximity probe from a sensor magnet in close proximity. For one thing it would be a static non-varying magnetic field. If we further look at the case of a varying magnetic field, thus a field able to create a voltage given the presence of a conductor in that field, then the chart below shows the effect of a 300 Gauss 60 Hz field on a proximity probe mounted on a generator. It shows that for 5-meter proximitor, probe and cable at a 50 mil gap, the total...
Topic

SKF Eddy Probe Compatibility

N Glover ·
It appears that the SKF CMSS 65 Eddy probes that we have used for years are no longer available! The new equivalent are CMSS 75 probes, but does anyone know if I could use a 75 probe, with the rest of a 65 system (Driver and Extension Cable)?
×
×
×
×